Our factory is one of the leading and professional manufacturers and suppliers of shutter door roll forming machine in China, owns its own factory, offering you discount products at low price. Well-known for its high quality and high precision, this Australia Shutter Door Roll Forming Machine deserve your trust. Australia Shutter Door Roll Forming Machine Australia Shutter Door Machine ,Australia Style Shutter Door,Australia Style Shutter Door Machine,Shutter Gate Roll Forming Machine, Australia Type Shutter Door Roll Forming Machine, Gavanized Garge Door Roll Forming Machine Botou Kaiyite Cold Bending Machinery Co.,Ltd. , https://www.chinacoldbendingmachinery.com
Diaphragm shock pressure gauge is composed of two parts: diaphragm isolator and pressure gauge. Widely used in petroleum, chemical, pharmaceutical, food, paper and other industries to measure the pressure of liquid medium with strong corrosive, high viscosity, easy crystallization and solid particles. Vibration-resistant diaphragm pressure gauges use durable pressure gauges because of their use of the table, which effectively eliminates the effects of medium pulsation and environmental vibration, making the instrument indicator stable and reliable, while also increasing the life of the instrument.
Second, the diaphragm pressure gauge structure principle
Third, the diaphragm pressure gauge installation precautions:
Diaphragm pressure gauge installation precautions
I. Introduction:
When the pressure of the measuring medium acts on the diaphragm, the diaphragm is deformed, compressing the sealing liquid of the pressure gauge pressure measuring system and causing it to form a pressure. When the rigidity of the diaphragm is small enough, it is also very small, and the pressure gauge pressure measuring system forms a pressure close to the pressure of the measuring medium.
1. Take pressure position selection (1) Avoid areas where the piping is bent, branches, and streams form vortices.
(2) When there are protruding objects (such as temperature measuring elements) in the pipeline, the pressure tap should be taken in front of it.
(3) When pressure must be taken in the vicinity of the regulating valve, if the pressure is taken in front of it, the distance from the valve should not be less than 2 times the pipe diameter; if the pressure is taken after that, the distance from the valve should not be less than 3 times. Pipe diameter.
(4) For a wide container, the pressure tap should be in an area where the fluid flow is smooth and vortexless. In short, the position of the pressure tap determined on the process flow should be able to ensure that the selected process parameters are measured.
2. Connection of catheters
The horizontal section of the connecting conduit should have a certain slope to facilitate the removal of condensed liquids or gases. When the measured medium is a gas, the catheter should be tilted to the direction of the pressure inlet; when the measured medium is a liquid, the catheter should be tilted to the direction of the pressure measuring instrument; when the measured parameter is a small differential pressure, the tilt The degree can be slightly larger. In addition, if the pipe is in the upper and lower corners, the drainage condensate device should be installed at the lowest point or the exhaust device should be installed at the highest point according to the medium in the pipe, so as to ensure that the condensation will not accumulate in the pipe for a long time. Liquids or gases affect the accuracy of the measurement. Condensate liquids or gases regularly.